Punching shear calculator to ACI 318-19 and Eurocode 2

Check two-way (punching) shear at interior, edge and corner columns of reinforced and post-tensioned flat slabs. We run ACI 318-19 22.6 and EN 1992-1-1 6.4 side by side, with every step shown, the minimum effective depth that passes, and a printable report, a PDF and a CSV.

Engineering disclaimer. This free tool is for preliminary checks and education only. It uses simplified code methods and your inputs, and it is not a substitute for project design. Results must be verified by a qualified structural engineer responsible for the project. Verify every result against the current code edition, national annex, authority requirements and the project drawings before use. Iron Axis accepts no liability for decisions or designs based on these results. Read the full disclaimer.
Column and slab
For edge columns, c1 is the side perpendicular to the slab edge.
Mean of the two top bar layers: h − cover − bar size.
Concrete and load
C40/50 → 40 MPa.
Ultimate load transferred through the slab at this column, less any load inside the critical perimeter.
Slab type
Eurocode 2 settings
√(ρly ρlz) over the column width plus 3d each side.
— of punching capacity used (ACI 318-19) Interior column · RC slab
Step-by-step working

Indicative only, not a design. The results follow the methods and clauses set out below and depend on your inputs. Check them against the project drawings, specifications and the code edition and national annex adopted for the project.

How we calculate

1. ACI 318-19 two-way shear (22.6, SI)

  • Critical perimeter b0 at d/2 from the column faces (22.6.4.1): interior 2(c1 + d) + 2(c2 + d); edge 2(c1 + d/2) + (c2 + d); corner (c1 + d/2) + (c2 + d/2) [1].
  • Non-prestressed slabs, Table 22.6.5.2: vc is the least of 0.33 λs λ √fc′, 0.17 (1 + 2/β) λs λ √fc′ and 0.083 (2 + αs d/b0) λs λ √fc′, with β the long-to-short column side ratio, αs = 40, 30 or 20 for interior, edge and corner columns, λs = √(2/(1 + 0.004d)) ≤ 1 and √fc′ ≤ 8.3 MPa [1].
  • Prestressed slabs at interior columns at least 4h from a discontinuous edge, with fpc between 0.9 and 3.5 MPa (22.6.5.5): vc is the lesser of 0.29 λ √fc′ and 0.083 (1.5 + αs d/b0) λ √fc′, plus 0.3 fpc + Vp/(b0 d), with √fc′ ≤ 5.8 MPa. Otherwise we use the non-prestressed table [1].
  • vu = Vu/(b0 d) is compared with φvc, φ = 0.75 [1].

2. EN 1992-1-1 punching (6.4)

  • Basic control perimeter u1 at 2d (6.4.2): interior 2(c1 + c2) + 4πd; edge 2c1 + c2 + 2πd; corner c1 + c2 + πd [2].
  • vEd = β VEd/(u1 d) (6.38) with β = 1.15, 1.4 or 1.5 from Figure 6.21N, or your own value [2].
  • vRd,c = 0.12 k (100 ρl fck)1/3 + 0.1 σcp, not less than vmin + 0.1 σcp, with k = 1 + √(200/d) ≤ 2, ρl ≤ 0.02 and vmin = 0.035 k1.5 √fck (6.47 and 6.3N, recommended values) [2].
  • At the column perimeter u0 (interior 2(c1 + c2); edge c2 + 3d ≤ c2 + 2c1; corner 3d ≤ c1 + c2), β VEd/(u0 d) ≤ vRd,max = 0.4 ν fcd with ν = 0.6(1 − fck/250) and fcd = αcc fck/1.5 (6.4.5(3)) [2].

3. Minimum depth and reports

  • The minimum d is found by bisection: the smallest effective depth, rounded up to the next millimetre, that passes each code with all other inputs unchanged.
  • Print gives a one-document report with inputs, results, working, date and disclaimer. Download PDF builds the same report as a PDF in your browser; nothing is sent to us. Download CSV gives the numbers for a spreadsheet.
S-820 Video

Watch: a short explainer

Punching Shear in PT Slabs: What Prestress Adds

What prestress contributes to punching shear capacity in a PT slab, and what still has to be checked at the columns.

What the calculator does

Punching shear is often the check that sets the thickness of a flat slab, and it is a brittle failure, so it gets close attention in every RC and PT flat slab we design or review. This calculator works through the two codes we use most, ACI 318-19 [1] and EN 1992-1-1 [2], for the same column, so you can see the control perimeter, the stresses, the resistance and the utilisation of each, and the minimum effective depth that passes without shear reinforcement.

ACI 318-19 or Eurocode 2: why the results differ

  • Control perimeter. ACI checks at d/2 from the column face; Eurocode 2 at 2d with rounded corners. The Eurocode perimeter is longer, and its stress limits are lower to match.
  • Reinforcement. Eurocode 2 rewards top steel through ρl; ACI 318-19 does not, but applies the size effect factor λs to deep slabs.
  • Moment transfer. ACI adds the γv Msc stresses from unbalanced moment explicitly. Eurocode 2 uses β, which this calculator applies through Figure 6.21N or your own value.
  • Prestress. ACI 318-19 gives interior columns of PT slabs a higher vc with 0.3 fpc and the tendon vertical component Vp. Eurocode 2 adds 0.1 σcp.

With light top steel the Eurocode check is often the more demanding of the two, as the default inputs show. Run both when a project allows either code.

How to use it

  1. Choose the column position and enter c1, c2, the slab thickness and the average effective depth of the top steel.
  2. Enter fc′ (the cylinder strength) and the factored column reaction. Subtract any load inside the critical perimeter if you want to be exact.
  3. For a PT slab, enter the average precompression and, for ACI, the vertical tendon component if you have it.
  4. Set the Eurocode 2 top steel ratio over the column, αcc and β.
  5. Read both utilisations, the column face check and the minimum d, then use Print, Download PDF or Download CSV.

Assumptions and limitations

  • Rectangular columns, slabs without shear reinforcement and concentric reaction. Unbalanced moment transfer in ACI, openings near the column, drop panels and column heads, and the design of studs or links are not covered.
  • Eurocode 2 values are the recommended ones. Check CRd,c, vmin, k1, αcc and vRd,max in the national annex for your project.
  • For background, worked examples and the shear reinforcement equations, read our guide to punching shear in PT slabs to ACI and EC2.

Sizing a slab first? Try the PT slab thickness calculator or the RC vs PT slab calculator. For the bars in the slab, use the ACI 318 development length or Eurocode 2 lap length calculators.

References

The codes the calculator follows, consulted on 16 November 2026. Clause numbers are given so you can check each step; always use the edition and national annex adopted for your project.

  1. American Concrete Institute: ACI 318-19 Building Code Requirements for Structural Concrete and Commentary: 8.4.4.2 (moment transfer by eccentric shear), 22.5.5.1.3 (size effect factor λs), 22.6.3.1 (limit on √fc′), 22.6.4 (critical sections for two-way shear), 22.6.5.2 and 22.6.5.5 (vc for non-prestressed and prestressed slabs) and 22.6.6 (shear reinforcement limits)
  2. CEN: EN 1992-1-1:2004+A1:2014 Eurocode 2: Design of concrete structures, Part 1-1: 6.2.2 (vmin, eq. 6.3N), 6.4.2 (control perimeters), 6.4.3 (β, Figure 6.21N, eq. 6.38), 6.4.4 (vRd,c, eq. 6.47) and 6.4.5 (vRd,max at the column face)

Part of our free engineering tools and design guides. Codes are referred to by clause where we are confident of the reference; always check the edition and national annex adopted for your project.

S-581 FAQ

Questions we are asked about this.

How do you calculate punching shear in a flat slab?

Find the control perimeter around the column (d/2 from the face in ACI 318, 2d in Eurocode 2), divide the factored column reaction by the perimeter times the effective depth to get the shear stress, and compare it with the code resistance of the concrete. If it fails, increase the depth, the column size or the top steel, add a drop panel, or provide shear reinforcement.

What is the punching shear capacity of a slab to ACI 318-19?

For a non-prestressed slab, vc is the least of 0.33 λs λ √fc′, 0.17 (1 + 2/β) λs λ √fc′ and 0.083 (2 + αs d/b0) λs λ √fc′ in MPa, multiplied by φ = 0.75. For a 500 mm square interior column, d = 200 mm and fc′ = 40 MPa, φvc is about 1.57 MPa.

What is vRd,c in Eurocode 2?

vRd,c = CRd,c k (100 ρl fck)^(1/3) + k1 σcp, not less than vmin + k1 σcp, with recommended CRd,c = 0.18/γc = 0.12, k = 1 + √(200/d) ≤ 2 and k1 = 0.1. It is checked on the basic control perimeter u1 at 2d from the column.

What β should I use for edge and corner columns?

Where the structure does not rely on frame action for lateral stability and adjacent spans differ by no more than 25%, EN 1992-1-1 6.4.3(6) allows β = 1.15 for interior, 1.4 for edge and 1.5 for corner columns. Otherwise calculate β from the moments using 6.4.3(3) to (5).

Does post-tensioning increase punching shear capacity?

Yes. In ACI 318-19 interior columns of PT slabs use vc = 0.29 λ √fc′ + 0.3 fpc + Vp/(b0 d) (or the αs equation if lower), within the limits of 22.6.5.5. In Eurocode 2 the precompression adds 0.1 σcp to vRd,c. Tendons banded over the columns also carry part of the load through their vertical component.

Can I print or save the results?

Yes. Print gives a clean report with the inputs, results, working, date and disclaimer. Download PDF creates the same report as a PDF in your browser, and Download CSV gives the figures for a spreadsheet. Nothing is uploaded to our server.