RC column design calculator: axial load capacity
Check the axial load capacity of a rectangular or circular reinforced concrete column to ACI 318-19 or Eurocode 2. See the steel ratio, the squash load, the design strength and utilisation, tie spacing and whether the column is short or slender, with every step shown.
Step-by-step working
Indicative only. Axial capacity only; moments, biaxial bending and slenderness effects need a full design.
How we calculate
1. ACI 318-19
- Po = 0.85fc′ (Ag − Ast) + fy Ast (§22.4.2.2). Pn,max = 0.80Po for tied and 0.85Po for spiral columns (Table 22.4.2.1); φ = 0.65 tied, 0.75 spiral for compression-controlled sections (Table 21.2.2) [1].
- Longitudinal steel 1% to 8% of Ag (§10.6.1.1), at least 4 bars in rectangular ties and 6 in spirals (§10.7.3.1). Tie spacing ≤ 16db, 48 tie Ø and the least dimension (§25.7.2.1). Spiral ratio ρs ≥ 0.45(Ag/Ach − 1) fc′/fyt (eq. 25.7.3.3).
- Slenderness may be neglected when kℓu/r ≤ 34 + 12(M1/M2) ≤ 40 for braced columns, or ≤ 22 for sway columns, with r = 0.3h or 0.25D (§6.2.5.1) [1].
2. Eurocode 2
- A column must resist at least the minimum eccentricity e0 = max(h/30, 20 mm) (§6.1(4)). We find NRd at that eccentricity by strain compatibility with the parabola-rectangle diagram and the strain limits of §6.1(5) and Figure 6.1, rather than using the pure squash load [2].
- Steel limits As,min = max(0.10NEd/fyd, 0.002Ac) and As,max = 0.04Ac (§9.5.2). Slenderness limit λlim = 20ABC/√n with the default A = 0.7, B = 1.1, C = 0.7 (§5.8.3.1) [2]. Rectangular columns are checked about the minor axis.
Worked example to ACI 318-19
A 400 × 400 mm tied column with 8Ø20 bars (Ast = 2,513 mm², ρ = 1.57%), fc′ = 30 MPa and fy = 420 MPa:
- Po = 0.85 × 30 × (160,000 − 2,513) + 420 × 2,513 = 4,016 + 1,056 = 5,072 kN.
- φPn,max = 0.65 × 0.80 × 5,072 = 2,637 kN. A factored load of 2,000 kN is 76% of this.
- Ties Ø10: spacing ≤ min(16 × 20, 48 × 10, 400) = 320 mm, which the calculator rounds down to 300 mm. kℓu/r = 1.0 × 3,000 / 120 = 25 ≤ 34, so slenderness can be neglected for a braced column with M1/M2 = 0.
Why Eurocode 2 gives a lower figure
With fck = 30 MPa and fyk = 500 MPa, the pure squash resistance of the same column is about 4,155 kN, but EN 1992-1-1 requires every column to carry its load at the minimum eccentricity h/30 or 20 mm. At e0 = 20 mm the calculator finds NRd ≈ 3,717 kN by strain compatibility. The two codes also use different load factors, so compare utilisations, not capacities.
What it does not do
- Design for applied bending, biaxial bending or second-order moments. A column that is slender, or carries significant moment, needs an interaction diagram and moment magnification (ACI 318-19 §6.6.4) or the nominal curvature method (EN 1992-1-1 §5.8.8).
- Seismic detailing to ACI 318-19 Chapter 18 or EN 1998-1.
For an existing column that has lost capacity, or a new load on an old structure, see our structural strengthening design service. To size the footing under the column, use the isolated footing calculator.
References
The codes and texts the calculator follows, consulted on 19 November 2026. Always use the edition and national annex you will actually rely on.
- ACI: ACI 318-19 Building Code Requirements for Structural Concrete: §6.2.5, §10.6, §10.7, Table 21.2.2, §22.4 and §25.7
- CEN: EN 1992-1-1:2004 Eurocode 2: §5.8.3.1, §6.1 and §9.5
Part of our free engineering tools and design guides. Results are for preliminary design and checking, and must be verified by a qualified structural engineer responsible for the project. Clauses are referred to where we are confident of the reference; always check the edition and national annex adopted for your project.
Questions we are asked about this.
How do you calculate the axial load capacity of a column?
To ACI 318-19, φPn,max = φ × 0.80 × [0.85fc′(Ag − Ast) + fy Ast] for a tied column, with φ = 0.65. For spirals use 0.85 and φ = 0.75.
What is the minimum steel in an RC column?
ACI 318-19: 1% of the gross area (and not more than 8%). Eurocode 2: the larger of 0.10NEd/fyd and 0.2% of Ac, and not more than 4% outside laps.
What is the maximum tie spacing in a column?
ACI 318-19 §25.7.2.1: the least of 16 bar diameters, 48 tie diameters and the least column dimension. Seismic zones need closer hoops.
When is a column slender?
ACI 318-19: when kℓu/r exceeds 34 + 12(M1/M2) (max 40) in a braced frame, or 22 in a sway frame. Eurocode 2: when λ exceeds 20ABC/√n.
Why is φ lower for tied columns?
Tied columns fail more suddenly than spirally reinforced ones, so ACI uses φ = 0.65 against 0.75, and also caps the strength at 0.80Po against 0.85Po.
Can I use this for a column with moments?
Only as a first check. Columns with significant moment need a P–M interaction diagram; we can help with that as part of a design review.
Send the drawings. Get an answer from our engineers.
WhatsApp or email the architectural or structural set, the location and what you need. The reply comes from the engineers who will do the work, with a proposed scope and programme.
- +971 52 118 2569
- Telephone
- +971 52 118 2569
- Office
- Al Warqa 1, Dubai, UAE
- Hours
- Sunday – Thursday, 09:00 – 18:00 GST