Punching Shear in PT Slabs: What Prestress Adds
What prestress contributes to punching shear capacity in a PT slab, and what still has to be checked at the columns.

Punching at the column is the failure mode that most often decides the thickness of a PT flat slab. How ACI 318-19 and Eurocode 2 treat it, what precompression and inclined tendons contribute, and when shear studs are needed.
What prestress contributes to punching shear capacity in a PT slab, and what still has to be checked at the columns.
Want the numbers for your own column? Our punching shear calculator runs ACI 318-19 and Eurocode 2 side by side for interior, edge and corner columns, with a printable report.
Punching shear is a brittle failure in which the column pushes through the slab along a truncated cone or pyramid. In post-tensioned flat slabs it often sets the minimum slab thickness, the column size or the need for drop panels and shear reinforcement. Precompression helps, and tendons draped over the column add an upward component that reduces the net shear. The two main codes in the region, ACI 318-19 (adopted in Saudi Arabia through SBC 304 and widely used in the UAE) and EN 1992-1-1, handle these effects differently.
ACI 318-19 checks a critical section b0 at d/2 from the column face, with straight sides and square corners (§22.6.4). EN 1992-1-1 checks a basic control perimeter u1 at 2d from the loaded area, with rounded corners (§6.4.2), plus a check of maximum shear at the column face u0. Because the perimeters and the stress expressions differ, the stresses from the two codes cannot be compared directly; only the final capacities can.
For two-way prestressed slabs meeting the conditions of §22.6.5.5 (no column closer to a discontinuous edge than four slab thicknesses, f'c used in the root not more than 35 MPa, fpc in each direction between 0.9 and 3.5 MPa):
vc = βp λ √f'c + 0.3 fpc + Vp / (b0 d) (MPa)
βp = lesser of 0.29 and 0.083(αs d / b0 + 1.5)
Here fpc is the average precompression in the two directions, αs is 40, 30 and 20 for interior, edge and corner columns, and Vp is the vertical component of the effective prestress crossing the critical section. Where the conditions are not met, the slab is treated with the nonprestressed expressions of §22.6.5.2 (the least of 0.33λ√f'c, the aspect-ratio and perimeter expressions, with the size effect factor λs), without the precompression term.
Unbalanced moment is transferred partly by flexure and partly by eccentric shear (γvMsc, §8.4.4.2), so the maximum stress at the critical section is vu = Vu/(b0d) + γvMscc/Jc. The design check is vu ≤ φvc with φ = 0.75.
vRd,c = CRd,c k (100 ρl fck)1/3 + k1 σcp ≥ vmin + k1 σcp
CRd,c = 0.18/γc, k = 1 + √(200/d) ≤ 2.0, ρl = √(ρly ρlz) ≤ 0.02, k1 = 0.1
(EN 1992-1-1 §6.4.4, recommended values; check the National Annex.) The applied stress is vEd = βVEd/(u1d), where β allows for moment transfer; the simplified values in §6.4.3(6) are 1.15 for interior, 1.4 for edge and 1.5 for corner columns in braced frames with similar adjacent spans. Inclined tendons crossing the control section give a favourable vertical component, Vpd, that can be deducted from VEd (§6.4.3(2) and note). Bonded tendons can also count towards ρl in some interpretations; check how the National Annex and your firm treat it.
Headed shear studs are the most common punching reinforcement in PT slabs because the rails sit easily between tendons. In ACI 318-19 (§22.6.6 and §22.6.8) the concrete contribution with headed studs is limited to about 0.25λ√f'c (MPa) and the maximum nominal stress to about 0.66√f'c; studs must extend until the stress on an outer critical section falls below the concrete-only limit, typically 0.17λ√f'c at d/2 outside the outermost studs. In EN 1992-1-1 (§6.4.5, eq. 6.52):
vRd,cs = 0.75 vRd,c + 1.5 (d/sr) Asw fywd,ef sinα / (u1 d), fywd,ef = 250 + 0.25d ≤ fywd (MPa)
with a maximum at the column face vEd,0 ≤ vRd,max, and the outer perimeter uout found where shear reinforcement is no longer required. Many stud systems hold European Technical Assessments that permit higher capacities than eq. 6.52; their documents then govern the design.
Indicative values. The ACI stud limits (0.25√f'c, 0.66√f'c, 0.17√f'c) are quoted as we understand ACI 318-19 Chapter 22. Check the clause and the λs and φ factors for your edition, and use the stud supplier's approval for proprietary systems.
Interior column 600 × 600 mm, slab 250 mm, d = 210 mm, f'c = 40 MPa (cylinder), fpc = 1.5 MPa, ignore Vp.
ACI 318-19: b0 = 4 × (600 + 210) = 3,240 mm. αsd/b0 + 1.5 = 40 × 210/3240 + 1.5 = 4.09, so 0.083 × 4.09 = 0.34 and βp = 0.29. The root uses f'c limited to 35 MPa:
vc = 0.29 × √35 + 0.3 × 1.5 = 1.72 + 0.45 = 2.17 MPa
φVc = 0.75 × 2.17 × 3240 × 210 / 1000 ≈ 1,107 kN
EN 1992-1-1: fck = 40 MPa, γc = 1.5, k = 1 + √(200/210) = 1.976, ρl = 0.5%, σcp = 1.5 MPa. u1 = 4 × 600 + 2π × 2 × 210 = 5,039 mm.
vRd,c = 0.12 × 1.976 × (100 × 0.005 × 40)1/3 + 0.1 × 1.5 = 0.12 × 1.976 × 2.71 + 0.15 ≈ 0.79 MPa
VRd,c = 0.79 × 5039 × 210 / 1000 ≈ 836 kN (before dividing VEd by β = 1.15)
The ACI and Eurocode figures are not directly comparable: the load factors (1.2D + 1.6L against 1.35G + 1.5Q), the material factors, the moment-transfer method and the perimeter all differ. The example shows the steps, not which code is more generous. In both codes, the inclined component of the tendons over the column (Vp or Vpd) often adds substantially, which is a good reason to keep banded tendons passing through or close to the column.
| Item | ACI 318-19 | EN 1992-1-1 |
|---|---|---|
| Control perimeter | b0 at d/2, square corners (§22.6.4) | u1 at 2d, rounded corners (§6.4.2) |
| Concrete strength term | βpλ√f'c, βp ≤ 0.29, f'c ≤ 35 MPa in root | CRd,ck(100ρlfck)1/3 |
| Precompression term | 0.3 fpc, fpc 0.9–3.5 MPa | 0.1 σcp |
| Inclined tendons | Vp/(b0d) added | Vpd deducted from VEd |
| Moment transfer | γvMscc/Jc | β factor (1.15/1.4/1.5 simplified) |
| Studs | vc ≤ 0.25√f'c, vn ≤ 0.66√f'c (indicative) | Eq. 6.52 or product ETA |
Our PT design review and preliminary PT design support services include punching checks at every column.
Part of our PT design guides. Codes are referred to by clause where we are confident of the reference, and coefficients marked indicative should be checked against the code text; always check the edition and national annex adopted for your project. Worked examples are illustrative, not designs.
Yes. ACI 318-19 adds 0.3fpc and the vertical tendon component Vp to the concrete stress, and Eurocode 2 adds 0.1σcp and lets the inclined tendon component reduce the design shear.
They use different control perimeters (d/2 against 2d), different load and material factors and different moment-transfer methods. Only the overall capacity checks are comparable.
The vertical component of the effective prestress force in the tendons crossing the critical section. Tendons draped over the column push upwards and reduce the net shear.
When the factored shear stress exceeds the concrete capacity, when seismic drift compatibility requires them, or when a thinner slab is preferred to drop panels.
ACI 318-19 uses fpc only between 0.9 and 3.5 MPa in the prestressed punching expression, so additional precompression above 3.5 MPa gives no further credit.
Yes. Part of the control perimeter within the shadow of an opening near the column is ignored in both codes, which can reduce capacity significantly.
Technical information only. This article is general engineering information to help you understand the subject. It is not design advice for a specific project, codes and authority requirements change, and worked examples are illustrative. Designs must be prepared and checked by a qualified structural engineer responsible for the project, to the code edition adopted for the project. Disclaimer · Terms of use.