PT slab thickness calculator

Enter the spans, loads and panel position to get a scheme-stage slab thickness for a PT flat plate, a flat slab with drop panels, or a slab on wide band beams. It shows the span/depth ratio used, what governs, and a quick punching shear flag. All results are indicative.

Engineering disclaimer. This free tool is for preliminary checks and education only. It uses simplified code methods and your inputs, and it is not a substitute for project design. Results must be verified by a qualified structural engineer responsible for the project. Verify every result against the current code edition, national annex, authority requirements and the project drawings before use. Iron Axis accepts no liability for decisions or designs based on these results. Read the full disclaimer.
System and panel
Spans and loads
200 mm slab PT flat plate

Indicative only, not a design. Thickness comes from published span/depth guidance with simple adjustments. Punching shear, deflection, vibration, fire, restraint, openings and the code your authority applies can all change the answer. Final sizes need a full design.

How we calculate

1. Span/depth ratio

  • h = L / (r × k × p), rounded up to 10 mm. The practical value is rounded up to 25 mm.
  • Base ratio r on the longer span, for interior panels with light loading: 45 for a PT flat plate and 50 for a PT flat slab with drop panels [1]. For slabs between band beams, r = 40 on the clear span between bands (published range 35 to 45) [1].
  • Load adjustment k = 1 − 0.04 × (SDL + LL − 3.0), limited to 0.60 to 1.00. The published ratios apply to about 1.9 to 3.4 kPa superimposed load [1]. The 4% per kPa reduction is our simplification of the trend in the Concrete Centre PT flat slab table [2].
  • Panel adjustment p: 1.00 interior, 0.90 edge and 0.85 corner. The 0.90 mirrors the ratio between the exterior and interior panel limits in ACI 318-19 Table 8.3.1.1 (ln/30 against ln/33) [3]. The corner value is our own allowance for the least continuity.
  • Minimums: 200 mm for PT flat plates and flat slabs (a common industry minimum covering fire, cover, tendon drape and punching [2]); 150 mm for slabs between band beams. Check fire resistance and axis distance for the rating you need.

2. Drop panels and band beams

  • Drop panels extend at least L/6 each way from the column centre (so about L/3 × L/3 on plan) and project at least h/4 below the slab, following ACI 318-19 8.2.4 [3]. As a starting point we suggest a projection of about h/2, rounded up to 25 mm.
  • Band beams run along the longer span on the column lines. Width is about the band spacing / 4.5 (published range 1/4 to 1/5 of the spacing [1]), at least 1.2 m. Depth is the larger of L / (28 × k × p) on the band span [1] and 2 × the slab thickness. If the band comes out deeper than 2.5 × the slab, we flag it, since 2.0 to 2.5 × is the usual economic proportion [1].

3. Precompression and strand estimate

  • Load balancing in each direction. Balanced load w = 0.70 × (self-weight + SDL), drape a = h − 80 mm, and P = w L² / 8a per metre, with a minimum precompression of 0.86 MPa [3]. We assume 150 kN effective per 15.2 mm strand and 1.102 kg/m, plus 5% for stressing tails and end zones.
  • We flag precompression above 3.5 MPa, which usually means a deeper slab, drops or bands would be more economical.

4. Punching shear flag (flat plates and drop panels)

  • wu = 1.2 (self-weight + SDL) + 1.6 LL. Vu = wu × (tributary area − critical-section area). Tributary area is LxLy for interior columns, half that for edge columns and a quarter for corner columns.
  • Critical perimeter b0 at d/2 from a square column, with d = h − 40 mm (at drop panels, h includes the drop).
  • Capacity: interior columns use vc = 0.29√f′c + 0.3 fpc (ACI 318-19 22.6.5.5, ignoring Vp). Edge and corner columns use 0.33√f′c, with f′c = 40 MPa and φ = 0.75 [3].
  • Unbalanced moment is allowed for with β = 1.15 interior, 1.4 edge and 1.5 corner, the values recommended in EN 1992-1-1 Figure 6.21N [4]. Flag = β Vu / φVc: up to 0.75 likely OK, 0.75 to 1.0 check, 1.0 to 1.5 shear studs likely, over 1.5 consider drops, bands or larger columns.
  • Not checked: openings near columns, slab edges, transfer of moment in detail, size effect, or the column strip layout. This is a flag, not a punching design.

5. Cross-check

For flat plates and drop panels we also show the depth interpolated from The Concrete Centre PT flat slab table (Eurocode 2 / TR43, C32/40, mid-range values) [2][5]. UK practice tends to be a little deeper than PTI-style ratios, so the two together give a sensible range.

Choosing a PT slab system

Most post-tensioned floors in the Gulf use one of three systems. The right one depends on span, load, punching shear at the columns, and how much depth the architecture allows.

  • PT flat plate. A uniform slab sitting directly on columns. It gives the flattest soffit, the simplest formwork and the lowest floor-to-floor height. Published guidance puts it at about span/45 for light loading where punching is not critical [1]. Punching shear at the columns usually sets the limit, so heavier loads or longer spans push the slab deeper or need shear studs.
  • PT flat slab with drop panels. Local thickenings around the columns increase punching capacity and the hogging lever arm, so the main slab can be thinner, about span/50 for interior panels [1]. Drop panels cost some formwork time and local headroom, but they are often the economical step up for spans of about 10 to 12 m or heavier loads.
  • PT slab with wide (band) beams. Shallow, wide beams run along one column line and the slab spans between them. Published guidance suggests bands about 1/4 to 1/5 of the band spacing wide and 2 to 2.5 times the slab depth, with the beams at about span/28 for normal loads [1]. This suits longer spans in one direction, such as car parks and offices.

How load changes the thickness

Span/depth ratios are only a starting point. As superimposed load rises, especially live load that cannot be balanced by the tendons, the economical ratio falls and the slab gets deeper [1]. The Concrete Centre PT flat slab data show the same trend: at 8 m span, the mid-range depth rises from 215 mm at 2.5 kPa imposed load to 310 mm at 10 kPa [2]. The calculator reduces the ratio by 4% for each kPa of SDL plus live load above 3 kPa, and shows the ratio it used so you can follow the arithmetic.

Edge and corner panels have less continuity, so they deflect more and attract larger unbalanced moments at the columns. We reduce the ratio for them. In practice one thickness is usually adopted for the whole floor, so check the governing panel.

Minimum thickness and fire

Below about 200 mm, a PT flat slab runs short of room for tendon drape, cover, top and bottom reinforcement and punching resistance. The Concrete Centre notes that 200 mm is the industry-standard minimum depth used in its PT tables [2]. The calculator applies 200 mm to flat plates and flat slabs and 150 mm to slabs between band beams, and says when the minimum governs. Fire resistance depends on the axis distance to the tendons as well as the thickness, so check the rating your authority requires; our fire resistance guide explains the rules.

The punching shear flag

For flat plates and drop panels, the calculator runs a simplified two-way shear check at the column, based on ACI 318-19 [3], with an allowance for unbalanced moment. If the flag says shear studs are likely, that is normal for many PT flat plates. If it says critical, it is usually better to look at drop panels, band beams or larger columns than to keep thickening the slab. The full method is explained in our punching shear guide.

To see what the chosen depth means for cost, weight and building height against a reinforced concrete slab, use the RC vs PT slab comparison calculator. For tendon drape and layout, see our tendon profile and layout guide.

Sources

Published guidance we used for the rules of thumb above, consulted on 13 November 2026. The numbers are paraphrased and simplified for scheme-stage use; they are not quoted design values.

  1. Z. Xia, STRUCTURE / Structural Engineer magazine, October 2008: “Efficient floor framing systems: preliminary sizing of post-tensioned floors” (span/depth about 45 PT and 30 RC flat plates, 50 and 35 with drop panels; wide shallow beams 1/4 to 1/5 of spacing, 2.0 to 2.5 × slab depth; beams about L/28)
  2. The Concrete Centre / J. Burridge, Concrete Quarterly, Spring 2020: “High tension: an introduction to specifying post-tensioned slabs”, Figure 1: span-to-depth ratios and rates for PT flat slabs
  3. American Concrete Institute: ACI 318-19 Building Code Requirements for Structural Concrete: Table 8.3.1.1 (minimum thickness of nonprestressed two-way slabs), 8.2.4 (drop panels), 8.6.2.1 (average precompression of at least 0.9 MPa), 22.6.5 (two-way shear strength)
  4. CEN: EN 1992-1-1 Eurocode 2, 6.4.3(6) and Figure 6.21N (recommended β = 1.15 internal, 1.4 edge, 1.5 corner columns)
  5. The Concrete Society: Technical Report 43, Post-tensioned concrete floors: design handbook (2nd edition, 2005)

Part of our tools and PT design guides. Codes are referred to by clause where we are confident of the reference; always check the edition and national annex adopted for your project.

S-531 FAQ

Questions we are asked about this.

What is the typical thickness of a PT flat slab?

For regular grids of about 7.5 to 9 m with normal loads, published guidance points to roughly 200 to 250 mm: about span/45 for light loading, with 200 mm a common minimum. Heavier loads, edge panels, punching shear and fire requirements increase it.

When should I use drop panels instead of a flat plate?

Consider drop panels when punching shear at the columns governs, when spans approach 10 to 12 m, or when loads are high. Drops increase the depth where shear and hogging moments peak, so the main slab can stay thinner. The calculator flags punching when a flat plate looks critical.

How wide and deep should PT band beams be?

A common starting point is a band width of about 1/4 to 1/5 of the band spacing and a depth of 2 to 2.5 times the slab thickness, with the band span/depth at about 1:28 for normal loads. The calculator uses these proportions and flags a band deeper than 2.5 times the slab.

Why does the calculator give a thicker slab for edge and corner panels?

End spans and corners have less continuity, so they deflect more and transfer larger unbalanced moments into the columns. We reduce the span/depth ratio by 10% for edge panels and 15% for corner panels. In practice, one floor thickness is usually chosen to suit the governing panel.

Can I use the calculator thickness in my design?

Only as a starting point for scheme design. A PT slab needs a full design covering load balancing, service stresses, deflection, punching shear, fire, restraint, openings and detailing to the code your authority applies. Send us your plans for a PT design review or a preliminary PT design.