Post-tension elongation calculator for PT tendons

Work out the calculated elongation of a post-tensioning tendon from its profile, the friction and wobble coefficients and the jacking force, for one-end or two-end stressing. See the force along the tendon before and after wedge draw-in, the reading to expect from the initial-load mark, and check a measured elongation against the ±7% band. Print the result or download it as a PDF or CSV.

Engineering disclaimer. This free tool is for preliminary checks and education only. It uses simplified code methods and your inputs, and it is not a substitute for project design. Results must be verified by a qualified structural engineer responsible for the project. Verify every result against the current code edition, national annex, authority requirements and the project drawings before use. Iron Axis accepts no liability for decisions or designs based on these results. Read the full disclaimer.
Strand and jacking force
Monostrand = 1.
ASTM A416 low-relaxation: 0.90fpu. EN Y1860S7: 1,640.
From the mill certificate of the strand batch. Default 195 GPa (EN 1992-1-1 §3.3.6 for strand); ACI 318-19 R20.3.2.1 notes 197 to 200 GPa as common design values.
ACI 318-19 Table 20.3.2.5.1: least of 0.94fpy, 0.80fpu and the anchorage supplier’s maximum.
Friction and wobble
Indicative values within the ranges in earlier ACI 318 commentary tables (monostrand μ 0.05–0.15; strand in metal duct μ 0.15–0.25, K 0.0016–0.0066 /m). EC2: μ from Table 5.1, k mid-range of §5.10.5.2. The approved PT system documents govern.
Tendon profile (from end A)
θ = sum of angle changes in the segment, vertical and plan. Parabola dropping e over b: θ = 2e/b. Set unused rows to 0.
Lock-off and site check
Wedge seating, from the PT system.
Only if elongation is read on the ram.
Load at which the mark is set.
From the initial-load mark, end A, before lock-off. 0 = not used.
ACI 318-19 §26.10.2(f): 7% force difference for post-tensioning; your specification may differ.
For gauge pressure. 0 = not used.
— calculated elongation P0
Step-by-step working

Indicative only, not a design or a stressing instruction. The results follow the methods set out below and depend on your inputs. Check them against the approved shop drawings, the PT system documents, the strand mill certificates and the jack calibration.

How we calculate

1. Jacking force

  • P0 = jacking stress × Ap × number of strands. ACI 318-19 Table 20.3.2.5.1 limits the stress during stressing to the lesser of 0.94fpy and 0.80fpu [1]; EN 1992-1-1 §5.10.2.1 recommends the lesser of 0.80fpk and 0.90fp0.1k [2]. The calculator warns when either is exceeded.

2. Friction and wobble along the tendon

  • ACI and PTI form: P(x) = P0 e^−(μθ + Kx), with θ the cumulative angle change in radians from the stressing end and K the wobble coefficient per metre [4]. EN 1992-1-1 eq. 5.45 writes the loss as P0 (1 − e^−μ(θ + kx)), so K = μk; k is generally 0.005 to 0.01 rad/m for internal tendons and Table 5.1 gives μ = 0.19 for strand [2].
  • The profile is entered as up to six segments with their length and angle change. Within a segment θ is taken to grow evenly, so μθ + Kx varies linearly and the force integral is evaluated exactly, segment by segment.

3. Elongation

  • Δ = ∫P(x) dx / (Ap Ep), which for one segment is Pavg L / (Ap Ep) with Pavg = P0 (1 − e^−a) / a and a = μθ + KL.
  • Two-end stressing: both ends are taken to the same jacking force; the point of no movement is where the friction exponent is half of the total, and each end elongates over its own side.
  • Strand inside the jack adds P0 Lj / (Ap Ep) when elongation is read on the ram. The reading expected from the initial-load mark is (Δ + Δjack) × (1 − Pi/P0), since elongation is proportional to force for the same friction profile.

4. Draw-in and lock-off

  • When the wedges seat, the strand slips back by Δset and friction reverses over the draw-in length xs. With the same coefficients the force after lock-off is P(xs)² / P(x) for x < xs, and xs is found by iteration so that the area between the two force curves equals Δset × Ap × Ep. If xs reaches the end of the tendon (or the point of no movement), the remaining draw-in is spread as a uniform drop. EN 1992-1-1 §5.10.5.3 sets out the same principle [2].
  • The force at the anchorage after lock-off is checked against 0.70fpu (ACI 318-19 Table 20.3.2.5.1) and the highest force after lock-off against min(0.75fpk, 0.85fp0.1k) (EN 1992-1-1 §5.10.3) [1] [2].

5. Site check and reports

  • A measured elongation (from the initial-load mark, before lock-off) is compared with the expected reading. ACI 318-19 §26.10.2(e) requires the force to be checked both by elongation and by the jack gauge, and §26.10.2(f) requires the cause of a difference of more than 7% between the force from elongation and the force from the jack gauge to be found and corrected for post-tensioned work [1] [3]. Gauge pressure = P0 / ram area, before the calibration chart correction.
  • Print gives a one-document report with inputs, results, the force diagram, working, date and disclaimer. Download PDF builds the report in your browser; nothing is sent to us. Download CSV adds the force profile at regular spacing.
S-820 Video

Watch: a short explainer

PT Elongation Doesn't Match the Calc? Check These 4

Measured elongation off from the calculated value? Check friction and wobble, the strand modulus, seating loss and initial slack before you call it a tendon problem.

What the calculator does

Once a tendon is locked off its force cannot be seen, so every stressing record compares the measured elongation with a calculated value. This calculator gives that value for a single tendon: the force along it after friction and wobble, the elongation at each stressing end, the effect of wedge draw-in on the lock-off force, the reading the crew should see from their initial-load mark, and whether a measured elongation falls inside the ±7% band. For the background read our guides to tendon elongation calculation, friction and wobble losses and elongation tolerances and records.

Post-tension elongation formula

Formulas used
ItemFormulaNotes
Jacking forceP0 = σj × Ap × nσj ≤ 0.80fpu and 0.94fpy (ACI); ≤ 0.80fpk and 0.90fp0.1k (EC2)
Force along the tendonP(x) = P0 e^−(μθ + Kx)EC2 eq. 5.45 uses μ(θ + kx), so K = μk
ElongationΔ = Pavg L / (Ap Ep)Pavg = P0 (1 − e^−a) / a, a = μθ + KL
Reading from the mark(Δ + Δjack) × (1 − Pi/P0)Δjack = P0 Lj / (Ap Ep) if read on the ram
Draw-in lengthArea between curves = Δset Ap EpApproximation: xs = √(Δset Ep Ap / p), p = friction loss per metre

Sources: [1], [2], [4]. The approximate draw-in formula in the last row is the one in our friction guide; the calculator iterates on the exact friction curve instead, so its draw-in length can differ slightly.

Worked example: 30 m monostrand slab tendon

The calculator defaults reproduce the illustrative example in our friction and elongation guides, so you can follow the numbers on screen. The values are assumed for explanation and are not taken from any project or PT system.

  • 15.2 mm strand, Ap = 140 mm², fpu = 1,860 MPa, Ep = 195 GPa, stressed to 0.80fpu: P0 = 1,488 × 140 = 208.3 kN.
  • Three 10 m segments with 0.272 rad each, μ = 0.06, K = 0.0033 /m: a = 0.06 × 0.816 + 0.0033 × 30 = 0.148, so the dead-end force is 208.3 × e^−0.148 = 179.7 kN.
  • Pavg = 208.3 × (1 − e^−0.148) / 0.148 = 193.6 kN and Δ = 193,600 × 30,000 / (140 × 195,000) = 213 mm.
  • With a 20% initial load, the reading from the mark should be about 0.8 × 213 = 170 mm, and the ±7% band is about 158 to 182 mm.
  • A 6 mm draw-in reaches about 13.0 m from the anchorage and leaves about 183 kN at the anchorage after lock-off, which is 70.3% of fpu, so the calculator flags the ACI 0.70fpu check for the engineer to review.

Stressing the same tendon from both ends gives about 110 mm at each end. On a 60 m tendon with the same curvature per metre, one-end stressing gives about 396 mm with the dead-end force down to 74% of P0, while two-end stressing gives about 213 mm at each end with the lowest force at 86% of P0. The designer decides the stressing ends; the numbers simply show why long tendons are often stressed from both ends.

Elongation records and charts

Search for a “post tension elongation chart” or “elongation report” and you will usually find a table of calculated elongations, one line per tendon, issued with the shop drawings. Run each tendon type through the calculator and download the CSV for its force profile and working. On site:

  • Agree the measuring method before stressing starts: mark on the strand at the initial load, or ram travel with the jack correction.
  • Use Ep and Ap from the mill certificates of the delivered strand; a 3% change in Ep moves the elongation by about 3%.
  • Compare like with like: readings at full pressure before lock-off do not include draw-in; readings after lock-off do.
  • Record the gauge pressure from the calibration chart of the jack and pump actually used.
  • Review the records before tails are cut or ducts are grouted, while re-stressing is still possible.

When the measured elongation does not match

Short readings usually point to higher friction than assumed, a kinked or misplaced profile, a jack or gauge out of calibration, or a strand modulus above the value used. Long readings can come from slack not taken up, slip at the dead end, a lower modulus or a broken wire. Check the measuring method and the certificates first, then the equipment, then the tendon. Our short video on this page walks through the four checks we start with, and our stressing support service covers calculated elongation tables and record reviews.

References

The codes the calculator follows, consulted on 19 November 2026. Always use the edition and national annex you will actually rely on.

  1. ACI Committee 318: ACI 318-19 Building Code Requirements for Structural Concrete: Table 20.3.2.5.1, §20.3.2.1 and §26.10.2(e)–(f)
  2. CEN: EN 1992-1-1:2004 Eurocode 2: Design of concrete structures, Part 1-1: §3.3.6, §5.10.2.1, §5.10.3, §5.10.5.2 (eq. 5.45, Table 5.1) and §5.10.5.3
  3. STRUCTURE magazine: Best Practices for Post-Tensioning Elongation Records (elongation records and the ±7% tolerance)
  4. Post-Tensioning Institute: Post-Tensioning Manual: friction and wobble coefficients and elongation calculation
  5. Post-Tensioning Institute: FAQ No. 6, Field elongation measurements (±7% and short tendons)

Part of our free engineering tools and design guides. Clauses are referred to where we are confident of the reference; always check the edition, national annex and PT system documents adopted for your project.

S-661 FAQ

Questions we are asked about this.

How do you calculate post-tension elongation?

Find the jacking force P0, work out the force along the tendon after friction and wobble, P(x) = P0 e^−(μθ + Kx), take the average force over the stressed length and divide: Δ = Pavg L / (Ap Ep). For a tendon with several curves, do it segment by segment and add the results.

What is the formula for PT tendon elongation?

Δ = Pavg × L / (Ap × Ep), where Pavg = P0 (1 − e^−a) / a and a = μθ + KL. For a 30 m monostrand tendon with P0 = 208.3 kN, Ap = 140 mm², Ep = 195 GPa and a = 0.148, Δ is about 213 mm.

What is the allowable elongation tolerance for post-tensioning?

ACI 318-19 §26.10.2(f) requires the cause of any difference of more than 7% between the force from measured elongation and the force from the jack gauge to be found and corrected for post-tensioned work. In practice this is applied as ±7% between measured and calculated elongation. Your specification may set a different value, and for tendons shorter than about 7.6 m (25 ft) the PTI suggests about ±6 mm (1/4 in) instead of a percentage.

Why is the measured elongation less than calculated?

Common causes are friction higher than assumed, a profile that differs from the drawings, jack or gauge calibration, a higher strand modulus than used in the calculation, or a different measuring method from the one the calculation assumed. Check the method and certificates before re-stressing.

What is wedge draw-in in post-tensioning?

When the jack releases, the strand pulls the wedges into the anchorage by a few millimetres (often around 6 mm, but the PT system sets the value). Friction reverses over the draw-in length near the anchorage, so the force there drops. The calculator finds that length and the lock-off force.

How do I calculate jack gauge pressure?

Divide the jacking force by the effective ram area: p = P0 / A. For example 208.3 kN on a 32 cm² ram gives about 65 MPa (651 bar). Always apply the calibration chart of the actual jack and pump.

Is the Eurocode wobble k the same as the ACI K?

No. EN 1992-1-1 eq. 5.45 multiplies k by μ, so the ACI/PTI wobble coefficient is K = μk. Using a Eurocode k as if it were K, or the reverse, is a common error. The calculator converts it for you.

Does stressing from both ends double the elongation?

No. Each end elongates over its own side up to the point of no movement. For a symmetric tendon the total is slightly more than for one-end stressing because the average force is higher, but each end moves about half as much.