Ultimate strength and secondary (hyperstatic) moments in PT members
At the ultimate limit state the tendon behaves like high-strength reinforcement, but its stress depends on bonding and the continuous structure carries extra moments created by the prestress itself. How to calculate fps, how to handle secondary moments, and a worked example of each.
Post-tensioned members are checked for flexural strength in much the same way as reinforced concrete: the factored moments must not exceed the design capacity of the section. Two things are different. First, the stress in the tendon at ultimate is not simply the yield stress: it depends on the effective prestress and on whether the tendon is bonded. Second, in a continuous structure the prestress creates support reactions, and with them secondary (hyperstatic) moments that must be included in the ultimate design. Both are frequent sources of error in design reviews.
Tendon stress at nominal strength
Bonded tendons. A bonded tendon strains with the surrounding concrete, so its stress at ultimate can be found from strain compatibility, or from the approximate ACI 318-19 §20.3.2.3.1 expression where fse ≥ 0.5fpu:
fps = fpu [1 − (γp/β1) (ρp fpu/f'c + (d/dp)(ω − ω'))], γp = 0.28 for low-relaxation strand
Unbonded tendons. An unbonded tendon is free to slide, so its strain increase is spread over its whole length and its stress at ultimate is much lower. ACI 318-19 §20.3.2.4.1 gives, for fse ≥ 0.5fpu:
Span/depth ≤ 35: fps = fse + 70 + f'c/(100ρp) ≤ fse + 420 and ≤ fpy
Span/depth > 35: fps = fse + 70 + f'c/(300ρp) ≤ fse + 210 and ≤ fpy (MPa)
Most PT slabs have span/depth ratios above 35, so the second expression applies. In EN 1992-1-1 §5.10.8(2), the stress increase in unbonded internal tendons may be taken as Δσp,ULS = 100 MPa (recommended value) if no detailed calculation of the deformation of the whole structure is made.
Worked example: unbonded slab tendon (illustrative)
Slab 220 mm, dp = 180 mm, span 8.4 m (span/depth = 38), f'c = 40 MPa, fse = 1150 MPa, Aps = 211 mm²/m so ρp = 211/(1000 × 180) = 0.00117.
fps = 1150 + 70 + 40/(300 × 0.00117) = 1150 + 70 + 114 = 1,334 MPa (≤ 1150 + 210 = 1,360 ✓)
a = Apsfps / (0.85f'cb) = 211 × 1334 / (0.85 × 40 × 1000) = 8.3 mm
Mn = 281.5 kN × (180 − 4.1) mm = 49.5 kNm/m φMn = 0.9 × 49.5 = 44.6 kNm/m
Bonded reinforcement added to satisfy §8.6.2.3 (see stress checks) also contributes and is added to the tension force. With the EC2 simplified Δσp,ULS = 100 MPa, the same tendon would be taken at about σpm,∞ + 100 ≈ 1,250 MPa, limited to fp0,1k/γs; with the different load and material factors, the two codes give similar but not identical results.
Secondary (hyperstatic) moments
In a statically determinate beam, the prestress produces a moment P × e at every section, called the primary moment. In a continuous beam or slab, the tendon tries to bend the member, the supports resist, and reactions develop. Those reactions create secondary moments that vary linearly between supports. The total prestress moment is:
Mtotal = Mprimary + Msecondary Mprimary = P × e
In the load-balancing method, the analysis of the balancing loads gives Mtotal directly, and the secondary moment is Mtotal − Pe. Design programs report it separately (RAM Concept calls it the hyperstatic load case; see our RAM Concept tips).
At ultimate, ACI 318-19 §5.3.11 requires the secondary effects to be included with a load factor of 1.0: Mu = 1.2MD + 1.6ML + 1.0Msec. The primary moment is not added, because the tendon is already counted as reinforcement in the capacity. EN 1992-1-1 applies γP = 1.0 to the prestress at ULS (§2.4.2.2) and includes the secondary effects in the same way.
Worked example: two-span beam (illustrative)
A two-span continuous beam with equal spans and a straight tendon at constant eccentricity e below the centroid, P = 1,000 kN, e = 100 mm.
- Primary moment everywhere: Pe = 100 kNm (hogging-type stress pattern: compression at the bottom).
- If the interior support were removed, the beam would camber upwards. Compatibility at the middle support gives a downward reaction R = 3Pe/L, and a secondary moment that grows linearly from zero at the ends to R × 2L / 4 = 1.5Pe at the interior support.
- Secondary moment at the interior support: 1.5 × 100 = 150 kNm, sagging.
- Total prestress moment at the interior support: −100 + 150 = +50 kNm, i.e. 0.5Pe in the opposite sense to the primary moment.
The example is extreme (real tendons are draped), but it shows why ignoring secondary moments can be unconservative: at interior supports of draped slabs the secondary moment is usually sagging and reduces the hogging capacity margin, and at midspan it adds to the sagging demand.
Moment redistribution
ACI 318-19 §6.6.5 permits redistribution of negative moments in continuous members, including prestressed ones, by up to 1000εt percent with a maximum of 20 percent, provided εt ≥ 0.0075 at the section where moment is reduced. Redistribution is applied to the moments including secondary effects. EN 1992-1-1 §5.5 sets its own limits based on xu/d.
Indicative values. Redistribution limits, the fps expressions and the EC2 100 MPa value are quoted from the codes as we understand them. Check each against the edition and National Annex adopted for your project.
Other strength checks
- One-way shear and punching (see punching shear).
- Minimum strength: ACI 318-19 §8.6.2.2 requires φMn ≥ 1.2Mcr for bonded tendons (with exceptions); check the clause for unbonded slabs.
- Ductility: tension-controlled sections (εt ≥ 0.005) for φ = 0.9.
- Transfer elements and beams with large prestress may need the strut-and-tie method (see PT transfer slabs and beams).
Summary
| Item | Rule | Reference |
|---|---|---|
| Bonded fps | Strain compatibility or approximate formula, γp = 0.28 | ACI 318-19 §20.3.2.3.1 |
| Unbonded fps, L/h ≤ 35 | fse + 70 + f'c/(100ρp), ≤ fse + 420 | ACI 318-19 §20.3.2.4.1 |
| Unbonded fps, L/h > 35 | fse + 70 + f'c/(300ρp), ≤ fse + 210 | ACI 318-19 §20.3.2.4.1 |
| Unbonded stress increase (EC2) | Δσp,ULS = 100 MPa (recommended) | EN 1992-1-1 §5.10.8(2) |
| Secondary moments at ULS | Load factor 1.0 | ACI 318-19 §5.3.11; EN 1992-1-1 §2.4.2.2 |
| Redistribution | 1000εt %, max 20%, εt ≥ 0.0075 | ACI 318-19 §6.6.5 |
We check strength, secondary moments and redistribution in every PT design review and design package.
Part of our PT design guides. Codes are referred to by clause where we are confident of the reference, and coefficients marked indicative should be checked against the code text; always check the edition and national annex adopted for your project. Worked examples are illustrative, not designs.
Questions we are asked about this.
What are secondary moments in post-tensioning?
Moments created by the support reactions that develop when a continuous member is prestressed. They vary linearly between supports and are added to the factored load moments at the ultimate limit state.
What load factor applies to secondary moments?
ACI 318-19 §5.3.11 uses a load factor of 1.0. Eurocode 2 uses γP = 1.0 for prestress at the ultimate limit state.
Why is fps lower for unbonded tendons?
An unbonded tendon slides within its sheathing, so its strain increase at failure is spread over its whole length rather than concentrated at the critical section, giving a smaller stress increase.
Which fps formula applies to most PT slabs?
Most slabs have span/depth ratios above 35, so ACI 318-19 uses fps = fse + 70 + f'c/(300ρp), capped at fse + 210 MPa and fpy.
Is the primary moment added to the ultimate moment?
No. The tendon is counted as reinforcement in the section capacity, so only the secondary moment is added to the factored load moments.
Can moments be redistributed in PT slabs?
Yes, within the code limits. ACI 318-19 §6.6.5 allows up to 1000εt percent, maximum 20 percent, applied to moments including secondary effects.
Technical information only. This article is general engineering information to help you understand the subject. It is not design advice for a specific project, codes and authority requirements change, and worked examples are illustrative. Designs must be prepared and checked by a qualified structural engineer responsible for the project, to the code edition adopted for the project. Disclaimer · Terms of use.